AirTerminal:SingleDuct:VAV:Reheat using ReverseWithLimits Damper Heating Action shows Maximum Flow Fraction During Reheat < 1 #10762
Labels
Defect
Includes code to repair a defect in EnergyPlus
Issue overview
Testing of VAV box using Damper Heating Action = ReverseWithLimits shows that a zone with heating dominated air flow rate has a Maximum Flow Fraction During Reheat < 1. This seems incorrect given that the VAV box should open to the full heating air flow rate when there is a heating load.
Defect file VAV terminal unit design:
The test file shows these results for zone design loads and air flow rates:
It would seem that for SPACE1, 3 and 5 that the Maximum Flow Fraction During Reheat would be 1 yet the results show otherwise:
This is likely due to the terminal unit considering:
Issue provided by Trane North America.