Power outlets: what a distribution panel hands on

Status: built, 2026-10-06. Issue #806. Builds on the power-port half of spec/tools/portrayal/dcim_export.py (PART_POWER) and on connectors-dc-terminal-design.md.

1. What existed, and what was missing

The exporter wrote power-ports: where a supply's cable is landed. It had no notion of a power OUTLET, which is where a device hands power on.

The first device this bit is the Amphenol Network Solutions 300CB08, a breaker panel. Two feeds come in, and sixteen circuits go out, each through one breaker position.

on the device exported before exported now
input-a, input-b - one feed each, both poles two dc-terminal power ports the same
breaker-a1 to breaker-b8 - sixteen positions sixteen module bays the same, each naming the output it protects
output-a1 to output-b8 - sixteen output circuits nothing; registered in NOT_A_DCIM_PORT sixteen power outlets

For a distribution panel the outlets are the fact a DCIM user most wants: which panel output a router's supply is cabled to, and which feed stands behind it.

2. What both targets offer

Read from each project's source: NetBox dcim/choices.py at 64ce9e2d, dcim/forms/object_import.py at 743b0683 and the component template models at 5707c0e9; Nautobot dcim/choices.py at 3edb1fca, dcim/forms.py at 6c1299e2 and the component template models at 3606c7da.

NetBox Nautobot
outlet type for a DC screw terminal dc-terminal dc-terminal
outlet type for a connector upstream does not name other other
the import key naming the feeding port power_port power_port, mapped to power_port_template "for backwards compatibility"
how that key is matched by name, among the same type's power ports the same
an outlet's description on import kept dropped: not in the import form
feed_leg A, B, C A, B, C
an outlet template may belong to a device type or a module type a device type or a module type
the feeding port must belong to the same device type or module type the same device type or module type

Consequences.

  • dc-terminal is in both, as an outlet type as well as a port type, and other is in both. No slug is invented. PART_OUTLET's values are checked against OUTLET_TYPES, that shared list, because Nautobot's component import turns an unknown type into other without a word.
  • One block serves both targets. Both read power_port by name and import power ports before power outlets, so for_target does not rewrite outlets.
  • An outlet and the port that feeds it live on one type. Both models' clean() refuse a port from another type, so an outlet on a breaker's module type could not name the panel's feed. The outlet is on the device type, which is also physically right: the BATT and RTN screws stay when a breaker is pulled, and a blank or fuse position keeps its terminals.
  • Nautobot loses the outlet's description. Its module-bay import keeps one, so the breaker sentence is written on the bay as well.

feed_leg is a phase of a three-phase supply. A panel's side A and side B are two feeds, not two legs of one, so feed_leg is not used for them. It would also collide by accident: the legs are spelled A and B.

Neither target links an outlet to a module bay. That a circuit is live only through the breaker in one position can be said in words and not as a relation.

3. Decisions

  1. An output circuit is a power outlet on the device type, with power_port set to the feed of its side.
  2. The manifest says which feed, on each placement. fed-by is stated per output and not on the group: nothing is inferred from a group or from an -a/-b in a name, and a panel whose outputs do not split cleanly by group needs nothing more.
  3. The manifest says which position, on the placement. through names the breaker position a circuit runs through, and is carried into the outlet's description and the bay's.
  4. feed_leg is not written for a two-feed DC panel.
  5. An outlet is named as its device's interfaces: rules name it, else by its placement id, as every exported port is: output-a1. The rules name power outlets as they name interfaces, so an outlet a rule names takes its printed label (the Eaton EVMI2130X's outlet-a1 exports as A1); an outlet no rule names keeps its placement id. A NOS listing that states its own interfaces does not apply these rules, so its export keeps every outlet's placement id.
  6. Outlets are a table row per part, as power ports are. A part exports outlets because PART_OUTLET lists it, not because of its class.
  7. A connectorized output is other, labelled. The 300CB08-C and -SC outputs are two-pole P40 receptacles, which neither target names; amphenol-ns/output-p40 maps to other with label: P40, the treatment OTHER_LABEL gives an interface whose form factor upstream does not name.
  8. Stating fed-by or through is a minor version; changing either is a major.

Rejected: for: (section 4), an attrs bag (nothing would check it), inferring the feed from -a/-b names, one outlet per screw (the two screws are one circuit's two poles, as a feed's two studs are one power port), outlets on the breaker's module type (section 2), and a hard-wired outlet type in the exporter instead of a table row.

4. The manifest

Two placement keys.

views:
  rear:
    components:
      placements:
        - {id: input-a,   ref: amphenol-ns/input-feed-studs@1, group: feeds, rel-pos: 1}
        - {id: output-a3, ref: amphenol-ns/output-terminal@1, group: outputs-a,
           rel-pos: 3, fed-by: input-a, through: breaker-a3}
  • fed-by names a placement on this device whose part exports a power port.
  • through names the bay that the circuit runs through: its breaker or fuse position. It is optional; a panel with fixed, unprotected outputs has none.

Where through names a FIXED breaker placement rather than a bay (#934, a rack PDU's branch breaker), the outlet description names that breaker as the unit prints it, Through breaker A, and not by its placement id: the first of the placement's attrs.label and attrs.section (the Eaton G4 tile letter) that is set, the id only when neither is (decided 2026-10-09; dcim_export.breaker_name). A bay position keeps Through breaker position <id>, since a bay prints nothing of its own.

Both are bare ids resolved over the whole device, because both cross a face: the output is on the rear and the position it runs through is on the front. A for: cannot say this. for: is a UI binding, emitted as data-for, saying "this mark or lamp annotates that", and it waives L13's overlap check between the two; it was not made for two parts on different faces with no drawing between them.

5. The export

# device-types/Amphenol Network Solutions/300CB08.yaml
power-ports:
  - {name: input-a, type: dc-terminal}
  - {name: input-b, type: dc-terminal}
power-outlets:
  - name: output-a1
    type: dc-terminal
    power_port: input-a
    description: Through breaker position breaker-a1
  # ... sixteen in all
module-bays:
  - name: breaker-a1
    position: breaker-a1
    description: 'Accepts: breaker-1ru, tpa-fuse-holder-307492, breaker-blank-1ru; protects output-a1'
  • PART_OUTLET = {"amphenol-ns/output-terminal": "dc-terminal", "amphenol-ns/output-p40": "other"}, beside PART_POWER, keyed on the ref for the reason PART_POWER is; OUTLET_LABEL gives the P40 its label.
  • A placement of a listed part becomes one outlet, and the rows are in natural order. Its power_port is the power port its fed-by names. A fed-by that names nothing exporting a power port stops the export (NotExpressible), because both targets reject a dangling reference at import. An outlet with no fed-by is written without power_port; it imports, and L134 counts it.
  • The same block is written for NetBox and for Nautobot (section 2).
  • amphenol-ns/output-terminal and amphenol-ns/output-p40 have left NOT_A_DCIM_PORT; the register's stale-entry test insisted on it.
  • The bay's added sentence does not move the module-type collision check: dcim_significant already reads a bay's description as a sentence about the drawing.

6. A module that carries outlets

Not needed by the 300CB08 and not built. It is the shape a rack PDU with a hot-swappable outlet module would need, and both targets allow it: the outlet template belongs to the module type. Its feeding port would have to be on the same module type, so it applies only to a module that has an input of its own. build_module would read PART_OUTLET the way it reads PART_POWER, and MODULE_PORT_KEYS would gain power-outlets with each row's power_port tokenised as its name is.

7. Lint

  • L132, fed-by resolves. It names a placement on this device whose part is in PART_POWER, and stands on a part in PART_OUTLET. An error.
  • L133, through resolves. It names a bay on this device, or, since #934, a placement of a part of class breaker fixed to the unit (a rack PDU's branch breaker, pdu-model-design.md section 5.3). An error.
  • L134, a part in PART_OUTLET is fed. Every placement of one states fed-by. A warning below verified and an error at it: an outlet with no feed is importable, and is the incomplete model this work exists to end.
  • L135, one position, one circuit. Two placements do not name the same through. A warning, because a panel that parallels two outputs behind one breaker is possible. It reads bays only: a fixed PDU breaker feeds many outlets by design (#934).

8. Device locks

fed-by and through are in devicelock's PLACEMENT_ADDRESSING, beside for. They change what is exported, not what is drawn. Stating one where there was none is a minor: the export gains outlets and loses nothing. Changing or dropping one re-files an imported outlet's feed and is a major. The three panels went to 1.1.0.

9. Tests

  • test_300cb08_power_outlets.py: each of the three panels exports sixteen outlets, eight naming each feed, each naming a position that exists and whose bay names it back, from the build and in the committed files of both trees, and both trees carry the same outlets.
  • test_power_outlets.py: an outlet whose fed-by names no power port stops the export; one with none is written without power_port; no feed_leg; the P40 label; OUTLET_TYPES.
  • test_silent_drops.py: the census knows the outlet exit, and nothing listed in PART_OUTLET is in NOT_A_DCIM_PORT.
  • test_power_outlet_lint.py: L132-L135.

10. Order of work

  1. Schema: fed-by and through on a placement; devicelock files them as addressing.
  2. Lint, section 7.
  3. Exporter: PART_OUTLET, the power-outlets block, the failing case.
  4. The 300CB08, 300CB08-C and 300CB08-SC: the two keys, the register entries removed, exports regenerated.

11. Open questions

  • AC. A rack PDU's C13 and C19 outlets have types in both targets and would use the same table. Whether a three-phase PDU states feed_leg per outlet is a question for the first one modelled. pdu-model-design.md (#934) proposes the answer: only for an outlet wired line to neutral on a wye input.
  • An alarm contact. The panel's Form C alarm relays have no port type in either target. They stay in NOT_A_DCIM_PORT.
  • Ratings. An outlet template in either target carries a type and no current rating. A feed rated in amperes at one of three nominal voltages has no honest single wattage, so no draw figure is written on the power ports either.
  • An unfed outlet in Nautobot. Its import form reads power_port from the submitted data before validating, so an outlet written without one has not been proved to import there. No device in the library writes one; L134 keeps it that way at verified.