update doc: HP total heating rate = sum coil heating rate
Browse files Browse the repository at this point in the history
previously it says HP total heating rate is the sum of air terminal heating
rate (which includes supplemental heating coil heating rate). This is wrong for
both the curve-based model and FluidTCtrl model. FluidTCtrl model doesn't have
an entry to this output field, so one is added.
  • Loading branch information
Yujie Xu committed Jul 26, 2024
1 parent 18f5c3f commit f5c5103
Showing 1 changed file with 5 additions and 1 deletion.
Original file line number Diff line number Diff line change
Expand Up @@ -619,7 +619,7 @@ \subsubsection{Outputs}\label{outputs-039}

\paragraph{VRF Heat Pump Total Heating Rate {[}W{]}}\label{vrf-heat-pump-total-heating-rate-w}

Check warning on line 620 in doc/input-output-reference/src/overview/group-variable-refrigerant-flow-equipment.tex

View workflow job for this annotation

GitHub Actions / build

Label `vrf-heat-pump-total-heating-rate-w' multiply defined.

This output field is the operating total heating capacity of the variable refrigerant flow heat pump in Watts. The capacity includes any degradation due to defrost mode. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. This value should match the sum of the individual zone terminal unit output variables for Zone VRF Air Terminal Total Heating Rate.
This output field is the operating total heating capacity of the variable refrigerant flow heat pump in Watts. The capacity includes any degradation due to defrost mode. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. This value should match the sum of the individual zone terminal unit heating coil output variables for Heating Coil Heating Rate.

\paragraph{VRF Heat Pump Cooling Electricity Rate {[}W{]}}\label{vrf-heat-pump-cooling-electric-power-w}

Expand Down Expand Up @@ -1153,6 +1153,10 @@ \subsubsection{Outputs}

Note: refer to the rdd file after a simulation for exact output variable names

\paragraph{VRF Heat Pump Total Heating Rate {[}W{]}}\label{vrf-heat-pump-total-heating-rate-w}

Check warning on line 1156 in doc/input-output-reference/src/overview/group-variable-refrigerant-flow-equipment.tex

View workflow job for this annotation

GitHub Actions / build

Label `vrf-heat-pump-total-heating-rate-w' multiply defined.

This output field is the operating total heating capacity of the variable refrigerant flow heat pump in Watts. The capacity includes any degradation due to defrost mode. This value is calculated for each HVAC system time step being simulated, and the results are averaged for the time step being reported. This value should match the sum of the individual zone terminal unit heating coil output variables for Heating Coil Heating Rate.

\paragraph{VRF Heat Pump Compressor Rotating Speed {[}rev/min{]}}\label{vrf-heat-pump-compressor-rotating-speed-revmin}

This output only applies for the VRF-FluidTCtrl model. This is the rotating speed of the compressor, which indicates the loading index.
Expand Down

5 comments on commit f5c5103

@nrel-bot-2
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

fixDocVRFheatpumpHeatRate (Unknown) - x86_64-Linux-Ubuntu-22.04-gcc-11.4: OK (3695 of 3695 tests passed, 0 test warnings)

Build Badge Test Badge

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

fixDocVRFheatpumpHeatRate (Unknown) - Win64-Windows-10-VisualStudio-16: OK (2862 of 2862 tests passed, 0 test warnings)

Build Badge Test Badge

@nrel-bot-3
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

fixDocVRFheatpumpHeatRate (Unknown) - x86_64-MacOS-10.18-clang-15.0.0: OK (3654 of 3654 tests passed, 0 test warnings)

Build Badge Test Badge

@nrel-bot-2c
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

fixDocVRFheatpumpHeatRate (Unknown) - x86_64-Linux-Ubuntu-22.04-gcc-11.4-IntegrationCoverage-Debug: OK (795 of 795 tests passed, 0 test warnings)

Build Badge Test Badge Coverage Badge

@nrel-bot-2b
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

fixDocVRFheatpumpHeatRate (Unknown) - x86_64-Linux-Ubuntu-22.04-gcc-11.4-UnitTestsCoverage-Debug: OK (2070 of 2070 tests passed, 0 test warnings)

Build Badge Test Badge Coverage Badge