DC power: an inventory, and a proposed model for DC ends and feeds

Status: proposed, 2026-10-15, for approval. Nothing here is built. The inventory (dc-power-inventory.md, written by spec/tools/dev/dc_inventory.py) is the only code in this change. The fix is the next order and starts only after the model in sections 5 to 8 is approved. Section 11 lists what needs a yes, and which published schemas it would republish.

Builds on cable-ends-design.md (a cable lands on a part of class port, or on a connector slot that takes one), connectors-power-design.md (AC), connectors-dc-terminal-design.md (lugs, plugs and studs) and power-outlets-design.md (what a panel hands on).

1. What went wrong

Wiring a rack's DC feeds with the assistant's tools, every feed was accepted, then flagged loose at both ends. Four parts showed it; the library's data for each:

part, in the build tried what it draws what is in the data why the end is loose
supermicro/psu-pws-601s-1r@1 two elements, terminal-rtn and terminal-48v, class inlet, and a ground screw the pole of each is in the element id and its description; the manual (MNL-2570 section 2.8) gives -48 V negative (battery), +Return positive, ground; 12 AWG an element is not a slot. "has no port terminal-48v" is true
nokia/lpwr-f@1 one element, connector-block, class terminal BAT at the left and RET at the right, each a two-stud terminal for a dual-hole lug, in a provenance sentence the same, and the block is one element for two terminals
amphenol-ns/nrg300cb08-sens (populated), output output-a1 amphenol-ns/output-terminal@1: elements batt and rtn BATT over RTN, #10-32, from the guide; fed-by: input-a, through: breaker-a1 output-a1/batt is an element id and an end names a slot. "is not on this panel"
ufispace/s9701-82dc (dc) ufispace/psu-132-dc@1: one element, terminal-block "Two poles (-48V and return)" in a sentence; no order, no side nothing says which post is -48 V and which is return

The parts DO state their terminals. They state them as art and as prose, which no tool reads as a cable end.

The port-usable checks (section 10 of part-conformance-design.md) judge a supply of class psu and a drawn terminal outside a seated module. nokia/lpwr-f@1 is class power, and its terminal block sits inside the module it fills, so those checks name no cause on it.

2. The inventory

python3 spec/tools/dev/dc_inventory.py --out docs/dc-power-inventory.md reads the source files (no build, seconds), lists every component contract that carries a DC end, and says for each what it draws, whether a cable lands on it today by the kit's own rule (cableEndsOf: a registered interface that a class port part mates, on the part or on a part it composes), the polarity a source states and the words that state it, and the source. It lists candidates by signal (attr, interface, element, part, name, hvdc, protector) and the reader of the output rejects what is wrong. Its test pins the logic on a small library and the real library on invariants only, so the fix does not have to rewrite it.

Counts, 2026-10-15 (library of 1,499 component contracts and 258 devices):

component contracts that carry a DC end 85
a cable lands on it today 8 yes (the P40 output, the two pluggable headers, the barrel jack, three terminal screws, the SR-1 pole pair), 12 through the parts it composes (9 of them HVDC supplies that land on their AC inlet), 63 no, 2 not applicable (protectors)
devices that place, offer or are fed by one 146: 27 land a cable, 103 do not, 16 are DC builds that draw their terminals as no part at all
placements of a DC end on a device face 225: 128 land (112 of them the P40 output), 5 through parts, 92 do not (64 are output-terminal)
polarity stated structured 10 parts, in a sentence only 40, nowhere 35

By kind: 22 supplies drawing a terminal block, 21 supplies whose DC end is not drawn at all, 6 supplies with a "DC inlet" of unspecified connector, 2 with a plug, 9 HVDC-capable supplies on their AC inlet, 6 terminal blocks, 3 screw terminals, 3 lug pairs, 2 pluggable headers, 3 plugs drawn already seated, 2 bus-bar inputs, one connector block, one barrel jack, one P40 output, 2 protectors, one other.

By vendor (parts): ufispace 12, nokia 10, common 10, edgecore 9, amphenol-ns 7, cisco 7, telco-systems 7, dell 6, juniper 6, commscope 3, casa 2, oscilloquartz 2, celestica 1, maiaedge 1, smartoptics 1, supermicro 1. By vendor (devices): ufispace 43, edgecore 27, telco-systems 13, amphenol-ns 11, nokia 11, aurcore 10, juniper 8, cisco 7, oscilloquartz 4, then eight vendors with one to three.

What it found that shapes the model:

  • The shapes are few. A pluggable connector with poles (P40, the 5.08 headers, the barrel jack, the telco plugs), a terminal block of screws or studs (one lug per conductor), a stud pair for one two-hole lug, and a bus-bar blade. The library already has a seat and a lug or plug for the first three.
  • Polarity is already in the data, in the wrong place. Ten parts state it in element ids or part ids (terminal-48v, a-neg, batt, wire-1 BATT), 39 in a sentence. Where the source is silent the library already declares it: the fuse panel's input says in a gaps entry (input-polarity, vendor-silent) that its two terminals are terminal-1 and terminal-2 "by position, not by polarity". That is the stand-in of section 5.6, found in use.
  • One DC terminal block is already modelled the way section 5 asks. nokia/sr-1-dc-terminal-block@1 composes four poles a-neg, a-rtn, b-neg, b-rtn, each a slot (stud-pair-5-8) that a two-hole lug lands on, and the printed legend and the guide name each. The model generalises it; it does not replace it.
  • Nothing in the library is a rectifier, a battery shelf or an Anderson-style connector. Searched by name and description. The 2-pin DC connector is the pluggable terminal (common/dc-terminal-plug-2@1, the telco plugs). The sources of a DC feed in the library are fuse and breaker panels and a chassis bus bar.
  • What it cannot see: a DC terminal that a device draws as panel decor, with no part (the inventory lists 16 such builds with the device's own gap note where it has one), and polarity printed on a photograph that no sentence reports.
  • Known limits, from a 20-part check by a reviewer: a supply that states HVDC only in its provenance (a few) is not listed; the + - earth wording of a header is read as "ground" only; the 2-position header is left out because its description calls it a relay output, which is a signal and not power; a PoE-on-coax data port is not a power end under this definition.
  • HVDC supplies take the AC inlet (9 parts), so they already land by a C14 or C20 and polarity does not arise. They are listed and left out of the model.

3. How AC power is cabled today

The pattern the DC model follows, in the order a cable meets it:

  1. An end is a connector slot. A part that states an interface registered in connectors.yaml is a slot on every device that places it (iec-c14, iec-c20, iec-c13, iec-c19, saf-d-grid, nema-5-20r, eaton-c39); the registry entry cites a standards.yaml entry for the figures. A part with no interface is art, whatever its class.
  2. A cord end is a part. generic/c13-plug@1 and its siblings are class port, mates the interface, and carry the cable point. The slot takes a cable end when a class port part mates it (takesCableEnd, kit/rack/cable-rules.js). The plug is derived from the slot and never stored; an end states plug only where the slot takes several (endPlug, ordered by rating-a).
  3. An end is a path. {item, path, view}; psu-1/module/inlet, outlet-rear-3. A zero-U PDU's outlets and a card's ports are answered from the catalogue (zeroUEnds, kit 0.38, 0.44).
  4. What the part IS comes from its attrs. receptacleOf reads attrs.outlet (hands power on), attrs.input (takes it), ac or dc where stated; couplerRole reads IEC numbering where nothing else does. spec/schemas/power-roles.yaml decides watts per CLASS: inlet is passive ("the supply behind it is what draws", and its note names dell/dc-terminal-6ryj9), psu and power are supplies with power-output-w, breaker is passive.
  5. A cable is one row. media: power is a cord or a DC feed, its type says which. power-c13 and power-c19 in cable-types.yaml give a conductor, an outside diameter and a bend radius, flagged unverified where one maker is the only source. A cord set pairs its ends (C13 to C14).
  6. Checks warn and refuse nothing (mismatch): data cable into a power end, AC against DC where both state it, two outlets or two inlets. A DC feed is the same warning at the same level.
  7. A panel states its wiring as data. fed-by and through on an outlet or an output (pdu-model-design.md section 5; power-outlets-design.md): output-a1 is fed-by: input-a, through: breaker-a1, the breaker's rating is a bay attribute. DCIM exports a power outlet and its power_port.
  8. The cables file leaves power out by reason (cable-ends-design.md section 7, item 8). Unchanged by this note.

4. What AC has and DC lacks

AC has DC has
a registered interface per receptacle, so a slot 8 of 85 parts; the rest are art or a supply that lands on its AC inlet
a cord end part per interface a ring lug, a two-hole lug, three terminal plugs, one barrel plug, one P40 plug; none for a terminal drawn as art
one slot per conductor group (a cord has 3 conductors and one inlet) one slot per SCREW; a feed lands on "the first free screw" (cable-ends-design.md section 3), so the end is not the terminal and a polarity cannot be asked of it
a direction (attrs.input, attrs.outlet) a direction only where attrs.input or the name says it; polarity as no field at all
a cord type per connector pair no DC cable type: no conductor roles, gauge, ampacity or colour
the voltage in the connector (C14 vs C20 rating is the plug's) the voltage in prose
fed-by and through on PDU and panel outlets fed-by, through on the fuse panel outputs only; load sides ("PS0 from feed A") in prose
nothing to check beyond family and direction the checks of section 6 all need the facts above

5. The proposed model

5.1 Pole and role

A pole is one conductor's landing: a screw, a stud, a stud pair a two-hole lug spans, a contact in a connector. Its role says which conductor of a DC circuit lands there, from a closed list kept in a registry file (spec/schemas/dc.yaml, vocabulary like connectors.yaml):

role what a source writes note
batt BATT, BAT, -48V, "negative (battery)", NEG the supply-side conductor of a negative-ground plant, at the end's stated voltage
rtn RTN, RET, return, "+Return", "positive (battery return)" the return
pos, neg +, - for a DC circuit with no battery wording (a 12 V or 24 V supply, the barrel jack)
gnd the earth symbol, PE a bonding conductor; stays media: ground and is not a pole of a feed

batt matches batt, rtn matches rtn, pos matches pos, neg matches neg; and batt matches neg, rtn matches pos on an end whose stated voltage is negative, because the Supermicro manual itself pairs them ("-48 Vdc negative terminal (battery)", "+Return positive terminal"). That table is data in dc.yaml with the source beside it. The sign is the end's voltage; the role is never a voltage.

5.2 A DC port: the thing a feed lands on

A part that takes or hands on DC states its DC ports, a new optional block on the contract:

dc:
  ports:
    - id: input                              # the end; its path is always the part's path + id, one port or several
      direction: input                       # input | output
      voltage: {nominal: -48, range: [-44, -65]}
      rating-a: 18                           # a supply's input current, a panel output's breaker comes from the bay
      awg: [12]                              # the conductor range the end takes, where a source gives one
      side: null                             # a | b where the part is one half of an A/B pair
      poles:                                 # ordered, one per conductor
        - {role: rtn,  slot: terminal-rtn}
        - {role: batt, slot: terminal-48v}
      source: {poles: terminals}             # the provenance key that says it; stand-in: see 5.6

A pole's slot names what the conductor lands on, in the part's own terms: a child part that presents a slot (a screw, a stud pair), a wire-N or cavity point of a pluggable connector (the P40 plug already has wire-1 BATT and wire-2 RTN), or, for a terminal drawn as art, an element that the fix turns into a seat part. Each DC port is published beside cages[] as dc-ports[] in components.json and each device's configs.json (path, direction, voltage, rating, awg, side, poles with their roles and slot paths). A device placement may override side, voltage, the roles of its poles and the rating-a, because the same part is the A feed in one place and the B feed in another (input-a, input-b) and a panel output takes its rating from the breaker in its bay.

A DC port takes a cable end when each pole's slot does (a pole slot takes a ring lug or a two-hole lug, a connector slot its plug). That is the existing rule, applied to the group; no pole needs a new cable-end part, and the P40, header and barrel cases are already done.

5.3 The shapes, in the library's words

shape pole is cable end at each pole exists today
terminal block of screws or studs a screw (terminal-stud) generic/ring-lug@1 the lug and two blocks; the SR-1's poles
stud pair for a two-hole lug a pair host (stud-pair-5-8 and its siblings) generic/two-hole-lug-*@1 yes (#828), the SR-1, the Nokia LPWR-F fits it
pluggable connector with poles a contact (wire-N) the connector's plug P40, 508-2/5/6, barrel
bus-bar blade a blade none held no: common/orv3-busbar-connector@1 and the fuse panel's input-feed-busbar need a blade end

5.4 A DC feed: one cable, or one per conductor

Recommendation: one cable per feed, N conductors in its type, landing on a DC port at each end. This keeps the decision cable-ends-design.md section 3 already made ("a DC feed is ONE cable of two conductors, landing on one terminal at each end and exported as one row"), and the reasons it gives hold:

  1. An installer runs, routes, labels and lengths a feed as one thing: "A feed to PSU-0". The route, the lay, the bundle, the fill and the label are per cable; two cables per feed double every figure and split what the installer reads as one.
  2. A fuse panel has 16 outputs; per-conductor cables would make 32 cables to name, route and fill.
  3. The DCIM power cable joins two power ports; a feed is one row.

How the other reading shows: each conductor is still a landing. Each end draws a lug (or a plug contact) per pole, and the cable's last stretch fans into the conductors (section 8). A conductor that runs alone (a return to a bus bar common to many loads, or a single-pole run to one terminal of a panel) is a feed of arity 1: the end names a pole, output-a1/batt, which is the failing address of section 1 and is valid in this model, because a pole is a child slot of its port. A cable type states how many conductors it has; a two-conductor feed lands on a port (all poles), a one-conductor feed on a pole. A ground wire stays media: ground. The rack file needs no new key.

Landing rules:

  • A feed's end addresses the port path (psu-0/module/input) or a pole path (.../batt). Today's rule, "the first free screw in natural order" (cable-ends-design.md section 3), goes away: the port is the end and its poles are taken together.
  • Conductor k of the cable lands on pole k, in the order the cable type gives them. Where both ends state their roles the kit matches by role; a feed whose roles cross is a polarity finding (section 6).
  • A port is free when no cable lands on it or on any of its poles. One pole taken by a single-conductor run makes the port partly used; a two-conductor feed to it is refused as taken, as a taken port is today.

5.5 Cable types

cable-types.yaml gains DC feed types in the family power (same media: power, so no rack key changes):

dc-feed-2x14awg:
  label: DC power feed, 2 x 14 AWG, ...
  media: power
  family: power
  dc: true
  conductors: [{role: batt, awg: 14}, {role: rtn, awg: 14}]
  ampacity-a: ...                     # from a table that is cited, or marked estimated
  od_mm: ...
  min_bend_radius: {installed: {xOD: ...}}

A type gives the conductor roles and the colour of each ONLY where a source does (the AC entries mark unverified what one maker states; the same rule). Gauges to start: those the library's ends state (12 AWG, 14 to 10 AWG, #6, 1.5 mm2). The kit reads od_mm and the bend radius as it does for every type. A cable with media: power and no type keeps its defaults (7.1 mm), as now.

5.6 A part whose source states no polarity

A declared stand-in, never a guess. The pole's role is written unstated, with:

- {role: unstated, slot: terminal-1, stand-in: {order: left-to-right}}   # on the port, not the pole: order is the port's

and the device carries a gaps entry (what: dc-polarity, reason: vendor-silent or needs-drawing, with wanted) exactly as the fuse panel's input does today. Lint refuses a role that has no source key and an unstated role with no gap. The surfaces show it as "?" on the pole and a note ("polarity of terminal-1 is not stated; checked by position"). The checks run by position and say so; nothing is warned as crossed on a stand-in, because the library does not know. A stand-in is never promoted to a role by a convention that merely sounds right ("BATT is on the left"): only a source does.

5.7 Sides and ratings

  • Side. An output or an input is side: a or b where its part is one half of an A/B pair: the fuse panel's two input feeds and the outputs they feed (fed-by), a chassis's feed A and feed B terminals (the Nokia SR-1 a-neg, the UfiSpace "two independent power circuits"), a load's PS0 from feed A (today a prose input attribute). On a load with a supply per feed the side is a property of the supply bay.
  • Rating. A source output's rating is the breaker or fuse in its bay (through: and the bay's rating or fuse-rating, already in the fuse panel's examples). A load's is its input current (current-max-a, input-voltage, already attributes on a dozen parts) or its maximum draw over the low end of its voltage range. A cable's is the type's ampacity-a.

6. The checks

All warnings, none a refusal, at the level of mismatch; each is said only where both sides state what it reads, and says what is missing otherwise. A polarity warning is first in the list.

check reads says
polarity matched end to end each pole's role on both ends "A is BATT where B is RTN": the feed is crossed. batt to batt, rtn to rtn (5.1 for the pairs)
the feed is to the right voltage each port's voltage: sign, nominal against the other's range "-48 V into a +24 V input"; "source nominal -48 V is outside the load's -40.5 to -57"
conductors against poles the type's conductors against the port's poles; the type's awg against the port's awg "a two-conductor feed to a three-pole port"; "14 AWG where the end takes 12"
A and B kept to their sides side on source and load, and the load's two supplies "both supplies of X are fed from side A"; "feed A lands on a B terminal"
a protector against the load the breaker or fuse rating, the load's current, the cable's ampacity "30 A breaker on a 40 A load"; "60 A breaker on a 14 AWG feed". Quiet where either side is not stated
direction direction of each port "both ends are outputs", as outlet to outlet is warned today
AC against DC as today unchanged

7. Schema, standards and cable types

file change published?
spec/schemas/component.schema.json the optional dc block of 5.2 (ports, voltage, rating, awg, side, poles with roles, the stand-in marker); additive, format unchanged yes, /schemas/v1/: needs a yes
spec/schemas/device.schema.json an optional per-placement dc override (side, voltage, rating, the roles of poles); additive yes, /schemas/v1/: needs a yes
spec/schemas/rack.schema.json none. A feed is media: power; an end is a path; the port path or a pole path are paths. Only the end.path and media descriptions get a sentence the text change republishes it if the sentence is wanted; skipping it costs nothing
spec/schemas/connectors.yaml none for the shapes that exist; the bus-bar blade needs one entry when its end is drawn no (tooling vocabulary)
spec/schemas/standards.yaml entries only where a figure is sourced: -48 V plant range, the terminal-block figures a vendor prints; nothing invented. Candidate sources to read and cite in the fix: the ETSI and ATIS documents for -48 V telecom plants no
spec/schemas/dc.yaml (new) the role vocabulary and the match table of 5.1, each pair with its source no
spec/schemas/cable-types.yaml the DC feed types of 5.5 no (compiled into cable-types.json)
spec/schemas/power-roles.yaml none. inlet and breaker stay passive; DC ports are not a class no
lint (lint.py) new rules, next free numbers: a role is in the vocabulary and has a source; a pole's slot resolves; a port's poles are all slots or all points; an unstated role has a gap; a voltage has a sign where it is negative no
DCIM exports none. A DC output remains a power outlet, an input a power port, as today; the cables file keeps leaving power out no
kit/ section 8; a minor version of the kit the kit is published

If no schema republish is preferred, the fallback is attrs on the part and the placement (dc-poles: 'rtn,batt', dc-side: a): no schema change, and unstructured; the library's experience with stud-size is that a text attribute is a fact "nothing reads". The recommendation is the schema.

8. How the surfaces show and offer DC ends

  • 2D (the panel). A DC port is drawn as it is: the lugs or plug on the poles. Each pole's role is a legend on the pole (-48V, RTN, ? for a stand-in), taken from the data and not from a colour. The port's hover reads "output-a1, BATT / RTN, -48 V, 30 A (breaker-a1), side A".
  • 3D. The lug seats already draw on terminal-stud, and the plug's wire-N points are the cable's landing (#805 is the pending work for routing to them). A feed ends at the port's mate and fans into its conductors over the last 10 to 30 mm (the stub lengths the plugs already use) to each pole's lug.
  • The cable editor. A free port is one row per DC port, not one per screw ("output-a1, -48 V BATT/RTN, 30 A") with its poles under it; freePorts gains ports and drops the of/first of 5.4. A DC feed shows its two ends' roles side by side and the findings of section 6 beside them; a crossed feed is red. The cable type picker offers the DC types when the first end is DC (the way proposeMedia offers power today).
  • The assistant's tools. ports.free lists DC ports with direction, voltage, side, rating and poles. cable.add accepts a port path or a pole path, resolves output-a1/batt and states which. cable.update and apply return the findings of section 6 in the same findings list. The failing messages of section 1 change from "has no port terminal-48v" to either the end it is or, for a part not yet modelled, "terminal-48v is drawn on this part but it declares no DC port; its poles are RTN and -48V in its provenance" (the part is named, and so is what is missing).
  • Parts not yet modelled keep working as now. An end on a part with no DC port is loose with the sentence above; nothing a rack file already holds is rewritten.

9. The four failing cases under the model

case what the contract gains the end
supermicro/psu-pws-601s-1r@1 one input port, -48 V (-44 to -65), 12 AWG, poles rtn on terminal-rtn and batt on terminal-48v (MNL-2570 section 2.8); the terminals become seats. The manual's supplied cable uses a Positronic CBD connector, so the plug is a connector, not a lug; the ground is media: ground, as it is psu-0/module/input or .../terminal-48v
nokia/lpwr-f@1 one input port, -40.5 to -72 V, 80 A; pole batt on a stud-pair-5-8 seat (BAT, left) and rtn on another (RET, right), UDS p96 and USIM p265 <bay>/module/input; each pole lands one dual-hole lug
amphenol-ns/output-terminal@1 an output port; poles batt (screw) over rtn (screw), #10-32, lug up to 0.5 in; the side from the placement's fed-by, the rating from the breaker in the bay output-a1, or output-a1/batt for a single conductor. The input pair is a stand-in: its terminals are terminal-1/terminal-2 "by position" and the existing input-polarity gap is its declaration
ufispace/psu-132-dc@1 one input port, -40 to -75 V, 40 A (the s9701-82dc device attribute), two poles whose roles are unstated until the guide's connecting-power figure is read; the device gap dc-polarity says so psu-0/module/input; the cable editor shows ?/? and the note

10. The fix's plan, with sizes

Sizes: S under a day of work, M a few days, L a week or more; counts are from the inventory.

step what size
1. Registry, schema, lint (landed: the dc blocks and lint rules L187 to L191; no library part carries a dc block yet, so this inventory, which reads interface and attrs, is unchanged) dc.yaml; the dc block in component.schema.json and the placement override in device.schema.json (after the yes); lint rules; tests with synthetic parts. No library part changes yet M, one PR
2. Build publish dc-ports[] in components.json and configs.json (render.py, components_index.py, the device index); the device lock treats a port as an export fact (a minor on a device that places one) M, one PR
3. Cable types the DC feed types, each sourced or marked estimated; cable-types.json S, one PR
4. Kit 0.48.0 (the kit on main now; the next minor if another has merged) cableEndsOf for a DC port, pole addresses, the DC free-port rows, the checks of section 6, the plug derived per pole, the assistant tools' text; every check_rack_* L, one or two PRs
5. Viewers the pole legends in 2D, the fan-out in 3D, the editor rows M, one PR
6. Library by vendor, each terminal with its source in this order (parts are the part's namespace; devices are those that place or offer one of those parts): (a) amphenol-ns and common: 17 parts, 36 devices, 221 placements; polarity already structured, the P40, headers and barrel already slots: S to M, two PRs. (b) supermicro and nokia: 11 parts, 10 devices, sources in hand: M. (c) ufispace: 12 supplies, 40 devices (+3 DC builds with no part); polarity mostly unstated, so mostly stand-ins plus a re-read of the guides: L, split by supply, the PSU-132 first because it is the S9701's. (d) edgecore, juniper, cisco: 20 parts, 29 devices (+4): L, three PRs. (e) telco-systems, dell, commscope, casa, oscilloquartz, smartoptics, celestica, maiaedge: 16 parts, 15 devices (+9): M to L. (The 9 HVDC supplies are out, section 11.) Each device takes a minor bump from the lock, and each PR is one vendor so its merge danger names one family. The 16 DC builds that draw their terminals as no part need a part drawn first: a separate list, S each M to L each, about nine PRs
7. A regression fixture the failing scenario of section 1 as a synthetic rack built from library parts: a panel's A and B outputs to two loads, one crossed and one not S

Order, not parallel: 1 before 2, 2 and 3 before 4, 4 before 6. 5 can follow 4 beside 6(a).

11. What needs a yes

  1. The recommendation of 5.4: one cable per feed, poles as child slots, arity 1 for a single conductor.
  2. The two schema changes of section 7: component.schema.json and device.schema.json, additive, each a republish of /schemas/v1/. Or the attrs fallback.
  3. The role vocabulary and its match table (5.1), in particular batt matching neg and rtn matching pos on a negative-voltage end.
  4. Stand-ins (5.6): a pole with no sourced role is unstated with a gap, and no check calls a feed crossed on it.
  5. HVDC through the AC inlet stays out of the model.
  6. A sentence on the rack schema's end.path and media (optional).

12. What this note does not do

It changes no part, device, schema, kit file or export. It does not read the standards it names as candidates; it cites no figure it did not find in a library file. It does not decide the 16 devices that draw their terminals as decor.