@roc-ops roc-ops commented Nov 21, 2026

Copy link
Copy Markdown
Owner

PREVIEW: needed (a new zero-U device drawn on every face: look at the front, the rear and the cord end)

Refs #1472

What this changes

Adds the Eaton EMA325-10, a zero-U three-phase managed rack PDU, drawn on its front, rear, both sides and both ends.
It has 18 C13 and 6 C19 outlets in three coloured sections, three 20 A two-pole breakers and a network module.
It adds two parts: eaton/g3-cord-l21-20p, the fixed input cord, and eaton/ema325-10-base, the well the face parts stand in.
The cord exports as an other power port labelled NEMA L21-20P, as the L5-30P cords do.
No existing part or device changes.

Sources

  • Eaton, "EMA325-10 G3 MANAGED" technical drawing (DWG EMA6PB15JGD88B1, rev 001, 4 Aug 2014, one A3 sheet): every size and position.
  • Eaton EMA325-10 product specifications page, pages 1 and 2: weight, input, outlets, cord length, outlet control.
  • Eaton ePDU G3 installation and connectivity quick start (P-164000314_2), page 2: the module's port legend. It is the generic G3 module and its sample display reads EMA305-10, a different model.
  • Not held, so not used: the Double-wide G3 quick start, the specification sheet, the eNMC replacement guide and the instruction set. The Visio stencil is held and was never opened.
  • No photograph of this model is held. The page's one picture is a person holding the strip, so it is no colour source.

Maturity claimed, and why

modelled. Every face is sourced to the drawing and each figure carries its provenance. It is not verified. The outlet pitch, the grips, the lamp size and the side fixings are estimates read off the render, and the device states the method.

Compared against the reference

I put each built face beside the drawing at matched scale, 4.377 px per mm, measured from the strip's own 1689 and 52.
The outlets, breakers, module, lamps and the long side agree with the sheet to within about 1 mm along the strip.
The three sections repeat to the pixel, so section B and C are section A moved 523.8 and 863.5 along the strip.
The built colours are a dark grey body, yellow, blue and red section outlines and strips, dark grey grips and dark unlit lamp lenses.
The breaker tiles are the sampled fills: yellow (248,232,64), blue (0,0,248) and red (248,0,0). They were counted at 16148, 15976 and 15931 pixels on a 300 dpi render.
No photograph is held, so the colours are checked against the drawing's own fills only.
Each outlet faces as the sheet draws it, with the earth slot away from the cord. The RJ-45 contacts and the buttons agree with the sheet.
Differences: the sheet's logotype is drawn as plain text, the mounting button is larger than drawn, and the lamps are dark lenses.
There is no "before" picture, as the device is new.

Gates run locally

  • Whole ./build.sh ran once and linted clean. The whole-library lint printed "LINT: no change against the baseline".
  • devicelock.py named only eaton/ema325-10 before --update, then showed 0 findings, and 0 against origin/main. The device is new, so it is at 0.1.0 with no bump.
  • preflight.py --write-exports wrote only this device's NetBox and Nautobot files, and library/exports is committed.
  • The new test module has 16 tests, each under 0.01 s. It passed with every file that names the device or the maker.
    The device, component and zero-U built sweeps passed too: 10563 tests in 193 files in all. The depth tests, the conformance report and the two named library-wide tests passed.
  • preflight.py --jobs 4 passed with no FAIL line.
  • A changelog fragment is added under changelog.d/.
  • No vendor material committed.

Test files moved: test_eaton_ema325_10.py (new) and test_occupant_turn.py. No version pin moves.
In test_occupant_turn.py the down count moves by one, from 257 to 258, and the device count by one, from 193 to 194. The one row is the ground screw on a washer. test_ground_stud_lugs.py needed no change.

Left out

Each item is a question to the maintainer.

  • The cord's loop, break line and plug beyond the strip's end are not drawn. The kit draws nothing beyond a face: lint L150 always reports a part beyond the face in height or along a side view. Is a loose cord to be drawn some day?
  • The breaker housing above the end view is not drawn, for the same reason. It stands 45.7 above the body, is about 209 long and has three handle bumps.
    The sheet prints the overall 4.4 [110.7] over it. Is the housing wanted as a body feature, or the overall depth recorded another way?

Merge danger

Door: two-way.

Blast radius: one new device and two new parts; the census pins move by one device. Nothing existing reads them.

Anything a reviewer should look at first

  • The mounting button part is larger than the sheet draws it: 24.7 across against 14.8. It is recorded as a gap.
  • The module's stacked RJ-45 pair is read as serial above and network below from the sheet's marks. That differs from the EMIT04-10's reading.
  • The strip's two long sides: the sheet shows one, read as the right face, and the left is built as the documented side.

Before and after pictures are shared with the maintainer separately.

🤖 Generated with Claude Code

roc-ops and others added 4 commits November 20, 2026 23:31
…se well

The strip is drawn on its front, rear, both sides and both ends from the maker's drawing. The cord exports as an other power port labelled NEMA L21-20P. The census pins move by the one ground screw it adds.

Refs #1472

Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
Signed-off-by: Jason Patterson <jpatterson@rocnetsupply.com>
Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
Signed-off-by: Jason Patterson <jpatterson@rocnetsupply.com>
…ten a skin comment

Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
Signed-off-by: Jason Patterson <jpatterson@rocnetsupply.com>
… file of its pair

The layout laid its decor, silkscreen and placement items out one key to a line, which made it larger than the device file it expands to. The items are now one per line in flow style, as the device file has them, with the same keys, order and values. The device file is unchanged.

Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
Signed-off-by: Jason Patterson <jpatterson@rocnetsupply.com>
roc-ops and others added 2 commits November 21, 2026 21:38
A part placed in a well is published at the well's floor, as far below the face as the well is deep. The census now subtracts that depth from the figure it derives. Seats outside a well are compared as before.

Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
Signed-off-by: Jason Patterson <jpatterson@rocnetsupply.com>
Signed-off-by: Jason Patterson <jpatterson@rocnetsupply.com>

This branch has not been deployed